Conductor: Flexible stranded copper wire. Class 2 acc/. UNE-EN 60228.
Insulation: EN 50363-1 - Silicone cross-linked rubber (SiR) type EI-2.
Identification: For > 5 conductors, Black Numbered + Yellow/Green, HD 308 S2 (Up to 5 Conductors)
Assembly: Concentrically assembled insulated conductors.
Outer cover: UNE-EN 50363-8 - Halogen-free TM-7 thermoplastic compounds for outer sheaths
Color: Orange
Operating voltage: 300/500V
Test voltage: 2.500V 5min
Operating temperature: -15...+90ºC (250ºC / 5 segundos en cortocircuito)
Standards:
(Construction) NF C 32-310 - Fire-resistant cables.
(Insulation) EN 50363-1 - Silicone cross-linked rubber (SiR) type EI-2.
(Sheath) UNE-EN 50363-8 - Halogen-free TM-7 thermoplastic compounds for outer sheaths
(Fire) UNE-EN 60332-1 (IEC 60332-1) - Flame-retardant.
(Fire) Cat. CR1 según / acc. NF C 32-070 - Fire resistant.
(Fire) UNE-EN 60754-1 (IEC 60754-1) - Halogen-free.
(Fire) Cat. C1 according to NF C 32-070 - Fire retardant.
(Fire) UNE-EN 60754-2 (IEC 60754-2) - Low corrosivity of smoke.
(Fire) UNE-EN 61034 (IEC 61034) - Low smoke emission.
CR1-C1 unshielded cables with intrinsic fire resistance to maintain service of security circuits during a fire, for example: signaling, detection and alarm circuits, circuits for evacuation and fire-fighting services, etc
With special fire characteristics that combine flame retardant features and a low heat emission with very low emission of smoke and hazardous gases.
Fill in the following fields to request the cable technical sheet in PDF format and the Declaration of Performance (DOP)