Conductor: Solid polished copper class 1 acc /. UNE-EN 60228
Insulation: EN 50363-1 - Silicone cross-linked rubber (SiR) type EI-2.
Identification: Colors according to VDE 0815.
Assembly: Pairs
Protector: Polyester ribbon.
2nd protector: Fibreglass tape.
Overall Shielding Al/Pet: Aluminium/Polyester Tape.
Overall Drain wire: Rigid tinned copper wire.
Outer cover: UNE-EN 50363-8 - Halogen-free TM-7 thermoplastic compounds for outer sheaths
Color: Orange
Operating voltage: 300/500V
Test voltage: 2.500V 5min
Operating temperature: -15... +90ºC
Standards:
(Construction) Based DIN VDE-0815 - Shielded telephone cables for indoor installations.
(Insulation) EN 50363-1 - Silicone cross-linked rubber (SiR) type EI-2.
(Sheath) UNE-EN 50363-8 - Halogen-free TM-7 thermoplastic compounds for outer sheaths
(Fire) EN 50200, IEC 60331-2 (para Ø < 20mm) - Intrinsic resistance: PH90 (90 minutes at 840°C).
(Fire) IEC 60331 / DIN VDE 0472-814 - Intrinsic resistance 180 minutes FE-180.
(Fire) UNE-EN 50575 - CPR
(Fire) UNE-EN 60754-2 (IEC 60754-2) - Low corrosivity of smoke.
(Fire) UNE-EN 61034 (IEC 61034) - Low smoke emission.
(Fire) UNE-EN 60332-1 (IEC 60332-1) - Flame-retardant.
(Fire) UNE-EN 60332-3 (IEC 60332-3) Cat C - Fire retardant.
(Fire) UNE-EN 60754-1 (IEC 60754-1) - Halogen-free.
(Tests) DIN VDE 4102 part 12 - Circuit integrity E30.
(Directives) 2011/65/EU - RoHS Directive (No use of toxic products).
(Directives) 2014/35/EU - Low Voltage Products European Directive.
Fill in the following fields to request the cable technical sheet in PDF format and the Declaration of Performance (DOP)