DATAX-COM Z1OZ1-K (AS) 300V CM/P/R

INSTRUMENTATION AND CONTROL  |  HALOGEN-FREE

DATAX-COM Z1OZ1-K (AS) 300V CM/P/R

Construction

Conductor: Flexible stranded copper wire. Class 5 acc/. NTP-IEC 60228.
Insulation: NTP - Halogen-free compound Z1.
Identification: Red, Black, White, Green, Brown, Blue
Assembly: Concentrically assembled insulated conductors.
Protector: Polyeste tape.
Overall Shielding Al/Pet: Aluminium/Polyester Tape.
Overall Drain wire: Stranded tinned copper wire acc/. UNE-13602
Shielding coverage: 100%
Outer cover: NTP - Halogen-free Z1 compound.
Color: Grey RAL-7001

DATAX-COM Z1OZ1-K (AS) 300V CM/P/R
RoHS RoHS
Halogen free Halogen free
Flexible cable Flexible cable
Low smoke opacity Low smoke opacity
Low gas corrosiveness Low gas corrosiveness
Fire retardant Fire retardant
Flame retardant Flame retardant
CE CE

Technical data / Regulations.

Operating voltage: 300/300V
Test voltage: 1000 V
Operating temperature: -15... +70ºC
Standards:
(Construction) Basado en la norma UL 444 - UL Standard for Safety Communications Cables.
(Insulation) NTP - Halogen-free compound Z1.
(Sheath) NTP - Halogen-free Z1 compound.
(Fire) NTP-IEC 60332-1 - Flame-retardant.
(Fire) NTP-IEC 60754-2 - Low corrosivity of smoke.
(Fire) NTP-IEC 60754-1 - Halogen-free.
(Fire) NTP-IEC 61034 - Low smoke emission.
(Fire) NTP-IEC 60332-3 - Fire retardant.

Observations

Part Number (X=type of packaging):

6003204C/X DATAXCOM Z1OZ1-K 2x0.34 mm² (22AWG)
6003404C/X DATAXCOM Z1OZ1-K 4x0.34 mm² (22AWG)
6003604C/X DATAXCOM Z1OZ1-K 6x0.34 mm² (22AWG)

Applications

Flexible cables based on the UL 444 standard, designed for use in the transmission of control, measurement and signaling signals.
With protection against electromagnetic interference.
With special fire characteristics that combine flame retardant features and a low heat emission with very low emission of smoke and hazardous gases. These cables help to increase the exhaust time and a less dangerous environment for rescue teams, this is essential to improve safety in public buildings such as hospitals, schools, shopping centers, railway stations, airports, etc.

Info request

Fill in the following fields to request the cable technical sheet in PDF format and the Declaration of Performance (DOP)

If you have any inquire, we are here to help you.