Conductor: Flexible stranded copper wire. Class 5 acc/. UNE-EN 60228.
Insulation: UNE-EN 21123-2 - XLPE polyethylene type DIX 3 according to HD 603-1.
Identification: HD 308 S2
Assembly: Concentrically assembled insulated conductors.
Filling sheath: UNE-EN 21123-2 - PVC type DMV-18 according to UNE-HD 603-1.
Armour: Steel wire armour (SWA).
Outer cover: UNE-EN 21123-2 - PVC type DMV-18 according to UNE-HD 603-1.
Color: Black
CPR classification: Eca
Operating voltage: 0,6/1KV
Test voltage: 3.500 V C.A. 5 min.
Operating temperature: -15...+90ºC (250ºC / 5 segundos en cortocircuito)
Standards:
(Construction) UNE-EN 21123-2 - Power cables for industrial use 0,6/1kV.
Cross-linked polyethylene insulation (XLPE) and polyvinyl chloride sheath (PVC).
(Fire) UNE-EN 60332-1 (IEC 60332-1) - Flame-retardant.
(Fire) UNE-EN 60332-3 (IEC 60332-3) Cat C - Fire retardant.
(Fire) UNE-EN 50575 - CPR
In case of single-core cables, the armor is made of a double aluminum tape, designated as RVFAV-K.
Flexible cable for the transport and distribution of electrical energy in fixed installations, protected or not.
Suitable for indoor and outdoor installations (requiring UV protection), on outdoor supports, in tubes or direct burial.
Especially adated to applications requiring mechanical and rodent protection thanks to its double steel tape armour overall protection. Special hydrocarbons resistant outer sheath.
Fill in the following fields to request the cable technical sheet in PDF format and the Declaration of Performance (DOP)