Conductor: Stranded tinned copper wire acc/. UNE-13602
Insulation: UNE-EN 50290-2-23 - Polyethylene for insulation.
Identification: White and Blue
Assembly: Pairs
Protector: Polyeste tape.
Overall Shielding Al/Pet: Aluminium/Polyester Tape.
Overall Drain wire: Stranded tinned copper wire acc/. UNE-13602
Braid Shielding: Tinned copper (Cu Sn) braid shielding.
Shielding coverage: 80%
Outer cover: UNE-EN 50290-2-27 - Halogen-free compound type Z1.
Color: Grey RAL-7001
CPR classification: Fca
Operating voltage: 300/300V
Test voltage: 1000 V
Operating temperature: -20... +70ºC
Standards:
(Construction) UNE-EN 50288-7 - Metallic cables with multiple elements used for the transmission and control of analogue and digital signals. Medium technical specification for instrumentation and control cables.
(Insulation) UNE-EN 50290-2-23 - Polyethylene for insulation.
(Sheath) UNE-EN 50290-2-27 - Halogen-free compound type Z1.
(Fire) UNE-EN 50575 - CPR
(Fire) UNE-EN 60754-2 (IEC 60754-2) - Low corrosivity of smoke.
(Fire) UNE-EN 61034 (IEC 61034) - Low smoke emission.
(Fire) UNE-EN 60332-1 (IEC 60332-1) - Flame-retardant.
(Fire) UNE-EN 60754-1 (IEC 60754-1) - Halogen-free.
Flexible cable designed to be used for data and signal transmission, for the cabling of instrumentation, equipment, and RS-485 automation systems. With protection against electromagnetic interference. In case of fire it does not emit any toxic substances or corrosive gases. It preserve public health and prevent any damage to electronic equipments.