Conductor: Flexible polished copper rope class V s/. UNE-EN 60228.
Insulation: EN 50363-3 - TI-1 PVC compound.
Identification: JZ: Black Numbered + Yellow/Green, OZ: Black numbered, JB: Color code + Yellow/Green, OB: Color code
Assembly: Concentrically wired insulated conductors.
Outer cover: EN 50363-4-1 - PVC compound type TM-2 for outer sheaths
Color: Grey RAL-7001
CPR classification: Eca
Operating voltage: 300/500V
Test voltage: 2.000V 5min
Operating temperature: -15... +70ºC
Standards:
(Construction) Based on DIN VDE 0245 - Cables for electrical and electronic equipment in electrical installations. PVC insulation and sheathing.
(Construction) UNE-EN 50525-2-51 - Low voltage electric cables. Cables of rated voltage less than or equal to 450/750V. General purpose cables. Oil-resistant control cables with thermoplastic insulation (PVC).
(Insulation) EN 50363-3 - TI-1 PVC compound.
(Sheath) EN 50363-4-1 - PVC compound type TM-2 for outer sheaths
(Fire) UNE-EN 50575 - CPR
(Fire) UNE-EN 60332-1 (IEC 60332-1) - Flame-retardant.
Fill in the following fields to request the cable technical sheet in PDF format and the Declaration of Performance (DOP)