Conductor: Flexible polished copper rope class V s/. UNE-EN 60228.
Insulation: UNE 21123 - Thermosetting ethylene-propylene elastomer (EPR).
Identification: HD 308 S2
Assembly: Concentrically wired insulated conductors.
Outer cover: UNE 21123 - Thermosetting polychloroprene rubber elastomer type SE1.
Color: Black
CPR classification: Eca
Operating voltage: 0,6/1KV
Test voltage: 3.500 V C.A. 5 min.
Operating temperature: -40...+90ºC (250ºC / 5 segundos en cortocircuito)
Standards:
(Construction) UNE 21166 / UNE 21150 - 0.6/1kV Flexible cables for mobile services / Cables for supplying submerged pumps for lifting water from wells.
(Insulation) UNE 21123 - Thermosetting ethylene-propylene elastomer (EPR).
(Sheath) UNE 21123 - Thermosetting polychloroprene rubber elastomer type SE1.
(Fire) UNE-EN 60332-1 (IEC 60332-1) - Flame-retardant.
Fill in the following fields to request the cable technical sheet in PDF format and the Declaration of Performance (DOP)