Conductor: Flexible stranded copper wire. Class 5 acc/. UNE-EN 60228.
Insulation: EN 50363-1 - Silicone cross-linked rubber (SiR) type EI-2.
Identification: Red / Black, Red / Black numbered
Assembly: Concentrically assembled insulated conductors.
Protector: Polyeste tape.
Individual Shielding Al/Pet: Aluminium/Polyester Tape.
Individual Drain wire: Stranded tinned copper wire acc/. UNE-13602
Outer cover: UNE-EN 21123-4 - Polyolefin LSZH.
Color: Red
CPR classification: Cca-s1b, d1, a1
Operating voltage: 300/500V
Test voltage: 2.500V 5min
Operating temperature: -15... +90ºC
Standards:
(Construction) UNE-211025 - Cables with intrinsic resistance to fire and intended for use in emergency circuits.
(Insulation) EN 50363-1 - Cables with intrinsic resistance to fire for use in safety circuits.
(Insulation) EN 50363-1 - Silicone cross-linked rubber (SiR) type EI-2.
(Sheath) UNE-EN 21123-4 - Power cables for industrial use 0,6/1kV.
Cross-linked polyethylene insulation (XLPE) and polyolefin sheath. / UNE-EN 21123-4 - Polyolefin LSZH.
(Fire) UNE-EN 50575 - CPR
(Fire) UNE-EN 60754-2 (IEC 60754-2) - Low corrosivity of smoke.
(Fire) UNE-EN 61034 (IEC 61034) - Low smoke emission.
(Fire) UNE-EN 60332-1 (IEC 60332-1) - Flame-retardant.
(Fire) UNE-EN 60332-3 (IEC 60332-3) Cat C - Fire retardant.
(Fire) UNE-EN 60754-1 (IEC 60754-1) - Halogen-free.
(Fire) EN 50200, IEC 60331-2 (for Ø < 20mm) - Intrinsic resistance: PH120 (120 minutes at 840°C).
Cables suitable for installation in premises in accordance with the Fire Safety Regulations in Industrial Establishments RSCIEI 2267/2004.
According to REBT 2002, it is suitable for the following installations:
ITC-BT 28 Public premises.
Flexible shielded cables with intrinsic fire resistance to maintain service of security circuits during a fire, for example: signaling, detection and alarm circuits, circuits for evacuation and fire fighting services, etc
With special fire characteristics that combine flame retardant features and a low heat emission with very low emission of smoke and hazardous gases.
With Aluminium/Polyester screen to protect against electromagnetic interference.