FIRE FR SZ1-K (AS+) 300/500V

FIRE & ALARM  |  FIRE RESISTANT CABLES

FIRE FR SZ1-K (AS+) 300/500V

Construction

Conductor: Flexible polished copper rope class V s/. UNE-EN 60228.
Insulation: EN 50363-1 - Silicone cross-linked rubber (SiR) type EI-2.
Identification: Red / Black, Red / Black numbered
Assembly: Concentrically wired insulated conductors.
Outer cover: UNE-EN 21123-4 - Polyolefin LSZH.
Color: Red or Orange

FIRE FR SZ1-K (AS+) 300/500V
CE CE
Flame retardant Flame retardant
Fire retardant Fire retardant
Low gas corrosiveness Low gas corrosiveness
Low smoke opacity Low smoke opacity
Flexible cable Flexible cable
Halogen free Halogen free
CPR Compilant CPR Compilant
RoHS RoHS

Technical data / Regulations.

CPR classification: Cca-s1b, d1, a1
Operating voltage: 300/500V
Test voltage: 2.500V 5min
Operating temperature: -15... +90ºC
Standards:
(Insulation) EN 50363-1 - Silicone cross-linked rubber (SiR) type EI-2.
(Insulation) EN 50363-1 - Cables with intrinsic resistance to fire for use in safety circuits.
(Sheath) UNE-EN 21123-4 - Power cables for industrial use 0.6/1kV. Cross-linked polyethylene insulation (XLPE) and polyolefin sheath. / UNE-EN 21123-4 - Polyolefin LSZH.
(Fire) EN 50200, IEC 60331-2 (for Ø < 20mm) - Intrinsic resistance: PH120 (120 minutes at 840°C).
(Fire) UNE-EN 50575 - CPR
(Fire) UNE-EN 60754-2 (IEC 60754-2) - Low corrosivity of smoke.
(Fire) UNE-EN 61034 (IEC 61034) - Low smoke emission.
(Fire) UNE-EN 60332-1 (IEC 60332-1) - Flame-retardant.
(Fire) UNE-EN 60332-3 (IEC 60332-3) Cat C - Fire retardant.
(Fire) UNE-EN 60754-1 (IEC 60754-1) - Halogen-free.

Info request

Fill in the following fields to request the cable technical sheet in PDF format and the Declaration of Performance (DOP)

If you have any inquire, we are here to help you.