FIRE FR SZ1-K (AS+) 300/500V

FIRE & ALARM  |  FIRE RESISTANT CABLES

FIRE FR SZ1-K (AS+) 300/500V

Construction

Conductor: Flexible stranded copper wire. Class 5 acc/. UNE-EN 60228.
Insulation: EN 50363-1 - Silicone cross-linked rubber (SiR) type EI-2.
Identification: Red / Black, Red / Black numbered
Assembly: Concentrically assembled insulated conductors.
Outer cover: UNE-EN 21123-4 - Polyolefin LSZH.
Color: Red or Orange

FIRE FR SZ1-K (AS+) 300/500V
CE CE
Flame retardant Flame retardant
Fire retardant Fire retardant
Low gas corrosiveness Low gas corrosiveness
Low smoke opacity Low smoke opacity
Flexible cable Flexible cable
Halogen free Halogen free
CPR Compilant CPR Compilant
RoHS RoHS

Technical data / Regulations

CPR classification: Cca-s1b, d1, a1
Operating voltage: 300/500V
Test voltage: 2.500V 5min
Operating temperature: -15... +90ºC
Standards:
(Insulation) EN 50363-1 - Cables with intrinsic resistance to fire for use in safety circuits.
(Insulation) EN 50363-1 - Silicone cross-linked rubber (SiR) type EI-2.
(Sheath) UNE-EN 21123-4 - Power cables for industrial use 0,6/1kV. Cross-linked polyethylene insulation (XLPE) and polyolefin sheath. / UNE-EN 21123-4 - Polyolefin LSZH.
(Fire) UNE-EN 50575 - CPR
(Fire) UNE-EN 60754-2 (IEC 60754-2) - Low corrosivity of smoke.
(Fire) UNE-EN 61034 (IEC 61034) - Low smoke emission.
(Fire) UNE-EN 60332-1 (IEC 60332-1) - Flame-retardant.
(Fire) UNE-EN 60332-3 (IEC 60332-3) Cat C - Fire retardant.
(Fire) UNE-EN 60754-1 (IEC 60754-1) - Halogen-free.
(Fire) EN 50200, IEC 60331-2 (for Ø < 20mm) - Intrinsic resistance: PH120 (120 minutes at 840°C).

Observations

Cables suitable for installation in premises in accordance with the Fire Safety Regulations in Industrial Establishments RSCIEI 2267/2004.
According to REBT 2002, it is suitable for the following installations:
ITC-BT 28 Public premises.

Applications

Flexible unshielded cables with intrinsic fire resistance to maintain service of security circuits during a fire, for example: signaling, detection and alarm circuits, circuits for evacuation and fire fighting services, etc
With special fire characteristics that combine flame retardant features and a low heat emission with very low emission of smoke and hazardous gases.