CONDEFLEX RZ1-K (AS) 0,6/1kV

ENERGY - LOW VOLTAGE  |  HALOGEN-FREE

CONDEFLEX RZ1-K (AS) 0,6/1kV

Construction

Conductor: Flexible stranded copper wire. Class 5 acc/. UNE-EN 60228.
Insulation: UNE-EN 21123-4 - XLPE polyethylene type DIX 3 according to HD 603-1.
Identification: HD 308 S2
Assembly: Concentrically assembled insulated conductors.
Filling sheath: UNE-EN 21123-4 - Polyolefin LSZH.
Outer cover: UNE-EN 21123-4 - Halogen-free polyolefin (type DMZ-E).
Color: Green or Black

CONDEFLEX RZ1-K (AS) 0,6/1kV
RoHS RoHS
CPR Compilant CPR Compilant
Halogen free Halogen free
Flexible cable Flexible cable
Low smoke opacity Low smoke opacity
Low gas corrosiveness Low gas corrosiveness
Fire retardant Fire retardant
Flame retardant Flame retardant

Technical data / Regulations

CPR classification: Cca-s1b, d1, a1
Operating voltage: 0,6/1KV
Test voltage: 3.500 V C.A. 5 min.
Operating temperature: -15...+90ºC (250ºC / 5 segundos en cortocircuito)
Standards:
(Construction) UNE-EN 21123-4 (IEC 60502) - Power cables for industrial use 0,6/1kV. Cross-linked polyethylene insulation (XLPE) and polyolefin sheath.
(Fire) UNE-EN 60754-2 (IEC 60754-2) - Low corrosivity of smoke.
(Fire) UNE-EN 60332-1 (IEC 60332-1) - Flame-retardant.
(Fire) UNE-EN 60332-3 (IEC 60332-3) Cat C - Fire retardant.
(Fire) UNE-EN 60754-1 (IEC 60754-1) - Halogen-free.
(Fire) UNE-EN 61034 (IEC 61034) - Low smoke emission.
(Fire) UNE-EN 50575 - CPR

Observations

According to REBT 2002, it is suitable for the following installations:
ITC-BT 09 Underground power networks for outdoor lighting installations.
ITC-BT 14 General power line.
ITC-BT 15 Individual derivation.
ITC-BT 20 Indoor installations or receiving stations.
ITC-BT 28 Public premises.


Allowable aid intensities for non-buried installations, with ambient temperature of 40° (UNE-HD 60364-5-52)

Applications

Flexible cable for the transport and distribution of electrical energy in fixed installations, protected or not. Especially designed for installations in public places where a safe reaction of the cable is required in case of fire, with low smoke opacity and minimizing the harmful effects of corrosive gas inhalation.
Suitable for indoor and outdoor installations (requiring UV protection), on outdoor supports, in tubes or direct burial.