Conductor: Flexible polished copper rope class V s/. UNE-EN 60228.
Insulation: EN 50363-7 - Halogen-free compound TI-7.
Identification: HD 308 S2
Assembly: Concentrically wired insulated conductors.
Outer cover: UNE-EN 50363-8 - Halogen-free TM-7 thermoplastic compounds for outer sheaths
Color: To be defined when ordering
CPR classification: Cca-s1b, d1, a1
Operating voltage: 300/500V
Test voltage: 2.500V 5min
Operating temperature: -15... +70ºC
Standards:
(Construction) UNE-EN 50525-3-11 - Flexible cables with halogen-free thermoplastic insulation and low smoke emission.
(Construction) UNE-EN 50525-2-11 - General purpose cables. Flexible cables with PVC thermoplastic insulation.
(Insulation) EN 50363-7 - Halogen-free compound TI-7.
(Sheath) UNE-EN 50363-8 - Halogen-free TM-7 thermoplastic compounds for outer sheaths
(Fire) UNE-EN 61034 (IEC 61034) - Low smoke emission.
(Fire) UNE-EN 60754-1 (IEC 60754-1) - Halogen-free.
(Fire) UNE-EN 60332-1 (IEC 60332-1) - Flame-retardant.
(Fire) UNE-EN 50575 - CPR
(Fire) UNE-EN 60754-2 (IEC 60754-2) - Low corrosivity of smoke.
(Directives) 2011/65/EU - RoHS Directive (No use of toxic products).
(Directives) 2014/35/EU - Low Voltage Products European Directive.
Fill in the following fields to request the cable technical sheet in PDF format and the Declaration of Performance (DOP)