Conductor: Flexible stranded copper wire. Class 5 acc/. UNE-EN 60228.
Insulation: UNE-EN 21123-2 - XLPE polyethylene type DIX 3 according to HD 603-1.
Identification: HD 308 S2 (Up to 5 Conductors), JZ: Black Numbered + Yellow/Green
Assembly: Concentrically assembled insulated conductors.
Overall Shielding Al/Pet: Aluminium/Polyester Tape.
Overall Drain wire: Stranded tinned copper wire acc/. UNE-13602
Inner Sheath: UNE-EN 21123-2 / IEC 60501-1
Armour: Steel wire armour (SWA).
Outer cover: IEC 60501-1 - Polyvinyl chloride type ST2.
Color: Black
CPR classification: Eca
Operating voltage: 0,6/1KV
Test voltage: 3.500 V C.A. 5 min.
Operating temperature: -15...+90ºC (250ºC / 5 segundos en cortocircuito)
Standards:
(Construction) UNE-EN 21123-2 - Power cables for industrial use 0,6/1kV.
Cross-linked polyethylene insulation (XLPE) and polyvinyl chloride sheath (PVC).
(Insulation) UNE-EN 21123-2 - Power cables for industrial use 0,6/1kV.
Cross-linked polyethylene insulation (XLPE) and polyvinyl chloride sheath (PVC). / UNE-EN 21123-2 - XLPE polyethylene type DIX 3 according to HD 603-1.
(Sheath) UNE-EN 21123-2 - Power cables for industrial use 0,6/1kV.
Cross-linked polyethylene insulation (XLPE) and polyvinyl chloride sheath (PVC). / IEC 60501-1 - Polyvinyl chloride type ST2.
(Fire) UNE-EN 60332-3 (IEC 60332-3) Cat C - Fire retardant.
(Fire) UNE-EN 60332-1 (IEC 60332-1) - Flame-retardant.
(Fire) UNE-EN 50575 - CPR
(Tests) UIC 895-or - Hydrocarbon Resistant.
(Directives) 2014/35/EU - Low Voltage Products European Directive.
(Directives) 2011/65/EU - RoHS Directive (No use of toxic products).
Suitable for electrical installations in premises classified as at risk of fire and explosion according to ITC-BT-029 of the Low Voltage Electrotechnical Regulations.
Flexible cable for the transport and distribution of electrical energy and control in fixed installations, protected or not.
Suitable for indoor and outdoor installations (requiring UV protection), on outdoor supports, in tubes or direct burial. With overall Aluminium/Polyester shielding to protect against interference and adapted to applications requiring mechanical and rodent protection thanks to its steel wire armour overall protection. Special hydrocarbons resistant outer sheath.
Fill in the following fields to request the cable technical sheet in PDF format and the Declaration of Performance (DOP)