Conductor: Flexible polished copper rope class V s/. UNE-EN 60228.
Insulation: UNE-EN 21123-2 - XLPE polyethylene type DIX 3 according to HD 603-1.
Identification: HD 308 S2 (Up to 5 Conductors), JZ: Black Numbered + Yellow/Green
Assembly: Concentrically wired insulated conductors.
Overall Shielding Al/Pet: Aluminium/Polyester Tape.
Overall Drain wire:
Inner Sheath: UNE-EN 21123-2 / IEC 60501-1
Armour: Steel wire armour (SWA).
Outer cover: IEC 60501-1 - Polyvinyl chloride type ST2.
Color: Black
CPR classification: Eca
Operating voltage: 0,6/1KV
Test voltage: 3.500 V C.A. 5 min.
Operating temperature: -15...+90ºC (250ºC / 5 segundos en cortocircuito)
Standards:
(Construction) UNE-EN 21123-2 - Power cables for industrial use 0.6/1kV.
Cross-linked polyethylene insulation (XLPE) and polyvinyl chloride sheath.
(Insulation) UNE-EN 21123-2 - Power cables for industrial use 0.6/1kV.
Cross-linked polyethylene insulation (XLPE) and polyvinyl chloride sheath. / UNE-EN 21123-2 - XLPE polyethylene type DIX 3 according to HD 603-1.
(Sheath) UNE-EN 21123-2 - Power cables for industrial use 0.6/1kV.
Cross-linked polyethylene insulation (XLPE) and polyvinyl chloride (PVC) sheath. / IEC 60501-1 - Polyvinyl chloride type ST2.
(Fire) UNE-EN 60332-3 (IEC 60332-3) Cat C - Fire retardant.
(Fire) UNE-EN 60332-1 (IEC 60332-1) - Flame-retardant.
(Fire) UNE-EN 50575 - CPR
(Tests) UIC 895-or - Hydrocarbon Resistant.
(Directives) 2014/35/EU - Low Voltage Products European Directive.
(Directives) 2011/65/EU - RoHS Directive (No use of toxic products).
Fill in the following fields to request the cable technical sheet in PDF format and the Declaration of Performance (DOP)