Conductor: Flexible stranded copper wire. Class 5 acc/. UNE-EN 60228.
Insulation: UNE-EN 21123-4 - XLPE polyethylene type DIX 3 according to HD 603-1.
Identification: HD 308 S2
Assembly: Concentrically assembled insulated conductors.
Filling sheath: UNE-EN 21123-4 - Polyolefin LSZH.
Inner Sheath: UNE-EN 21123-4 / UNE-EN 21123-4
Armour: Corrugated steel tape.
Outer cover: UNE-EN 21123-4 - Halogen-free polyolefin (type DMZ-E).
Color: Green
CPR classification: Cca-s1b, d1, a1
Operating voltage: 0,6/1KV
Test voltage: 3.500 V C.A. 5 min.
Operating temperature: -40...+90ºC (250ºC / 5 segundos en cortocircuito)
Standards:
(Construction) UNE-EN 21123-4 (IEC 60502) - Power cables for industrial use 0,6/1kV.
Cross-linked polyethylene insulation (XLPE) and polyolefin sheath.
(Insulation) UNE-EN 21123-4 - Power cables for industrial use 0,6/1kV.
Cross-linked polyethylene insulation (XLPE) and polyolefin sheath. / UNE-EN 21123-4 - XLPE polyethylene type DIX 3 according to HD 603-1.
(Sheath) UNE-EN 21123-4 - Power cables for industrial use 0,6/1kV.
Cross-linked polyethylene insulation (XLPE) and polyolefin sheath. / UNE-EN 21123-4 - Halogen-free polyolefin (type DMZ-E).
(Fire) UNE-EN 61034 (IEC 61034) - Low smoke emission.
(Fire) UNE-EN 50575 - CPR
(Fire) UNE-EN 60754-2 (IEC 60754-2) - Low corrosivity of smoke.
(Fire) UNE-EN 60332-1 (IEC 60332-1) - Flame-retardant.
(Fire) UNE-EN 60332-3 (IEC 60332-3) Cat C - Fire retardant.
(Fire) UNE-EN 60754-1 (IEC 60754-1) - Halogen-free.
(Directives) 2014/35/EU - Low Voltage Products European Directive.
(Directives) 2011/65/EU - RoHS Directive (No use of toxic products).
The armor of single-core cables is made of corrugated aluminum tape.
According to REBT 2002, it is suitable for the following installations:
ITC-BT 07 Underground distribution networks.
ITC-BT 09 Underground power networks for outdoor lighting installations.
ITC-BT 20 Indoor installations or receiving stations.
ITC-BT 29 Premises with risk of fire or explosion.
Allowable aid intensities for non-buried installations, with ambient temperature of 30° (UNE-HD 60364-5-52)
Cables for the transport and distribution of electrical energy and control in fixed installations, protected or not. Especially designed for installations in public places where a safe reaction of the cable is required in case of fire, with low smoke opacity and minimizing the harmful effects of corrosive gas inhalation.
Suitable for indoor and outdoor installations (requiring UV protection), on outdoor supports, in tubes or direct burial.
With a corrugated steel armour as mechanical protection